ATTACHMENT 1
(This attachment was originally
sent as an official letter summarizing the results of a NIOSH inspection
and testing of a self-contained breathing apparatus.)
DEPARTMENT OF HEALTH &
HUMAN SERVICES
Public Health Service
Centers for Disease Control
and Prevention (CDC)
National Institute for
Occupational Safety and Health - ALOSH
1095 Willowdale Road
Morgantown, WV 26505-2888
NIOSH Reference: TN-11336
Phone: (304) 285-5907
Fax: (304) 285-6030
February 1, 2000
Dear Chief:
The National Institute for
Occupational Safety and Health (NIOSH) has concluded its investigation
conducted under NIOSH Task Number TN-11336. This investigation consisted
of the inspection and testing of one self-contained breathing apparatus
(SCBA) shipped to NIOSH by the Fire Department on January 3, 2000. Our
inspection report and results of all tests are contained in a detailed
Status Investigation Report which is enclosed.
Inspection of the SCBA was
completed on January 4, 2000. The SCBA was worn and had the appearance
of having seen considerable use. Although the NIOSH approval label was
missing, and component part numbers could not be identified on a few component
parts, the SCBA appeared to be in the approved condition for a Mine Safety
Appliances (MSA) Ultralite, 30-minute, 2216 psi, SCBA (NIOSH approval number
TC-13F-138).
The SCBA was thoroughly inspected
and determined to be in a condition safe for testing. However, a current
hydrostatic test date was not identified on the fiberglass-wrapped composite
aluminum cylinder shipped with the SCBA. The cylinder was also found to
contain a substantial amount of fluid. It was subsequently learned that
the SCBA was left at the fire scene for several days following the fire
incident and was immersed in several inches of water. The fluid inside
the cylinder is believed to be water which seeped through the pneumatic
system of the SCBA and into the cylinder. The cylinder shipped with the
SCBA was determined to be unsafe for refilling. A substitute cylinder was
obtained from MSA for use during the testing of the SCBA.
The SCBA was tested in the
condition as received from the Fire Department (except for the replacement
cylinder). The purpose of the testing was to determine the SCBA’s conformance
to the approval performance requirements of Title 42, Code of Federal Regulations
(CFR), Part 84, Subpart H. Further testing was conducted to determine conformance
to the National Fire Protection Association (NFPA) Air Flow Performance
requirements of NFPA 1981, 1997 Edition. A series of tests utilizing a
Biosystems PosiChek3 computerized SCBA performance tester was also conducted.
Of the six selected NIOSH
tests performed, the unit failed the Rated Service Time Test and the Remaining
Service Life Indicator Test. The SCBA also failed to meet the minimum facepiece
pressure requirements of the NFPA Air Flow Performance Test. When performance
tested using the Biosystems PosiChek3, the unit failed the Alarm Accuracy
portion of the Complete SCBA Test.
During the inspection of
the SCBA, it was noted that paper fibers were adhered to the facepiece
exhalation valve diaphragm. At the time, no effort was made to remove these
fibers. During the Rated Service Time Test, the sound of air escaping from
the exhalation valve was observed after the cylinder valve was opened,
but prior to the start-up of the breathing machine. The unit failed to
meet the requirements of the Rated Service Time Test. After the performance
testing was completed, the exhalation valve was purged with compressed
air to remove the visible paper fibers. The Rated Service Time Test was
then repeated. This time, no air was observed to be leaking from the exhalation
valve, and the unit met the requirements of the test.
Internal inspections of other
individual components requiring disassembly (such as the low air alarm
assembly) were not performed.
The status of the SCBA with
regard to its conformance to the performance standards prior to the incident
cannot be determined. It is quite possible that the test failures observed
during this evaluation are a result of damage sustained by the SCBA after
the firefighter succumbed to his injuries while fighting the fire on December
18, 1999. For example, the paper fibers affecting the operation of the
exhalation valve could have been deposited when the SCBA was submerged
in water after the incident. It is also not known what effects, if any,
non-conforming SCBA performances would have had at the fire scene. While
the unit failed to maintain positive pressure during the NFPA Air Flow
Performance Test, the possibility of inward leakage into a firefighter’s
facepiece would be dependant upon the face to facepiece seal, the ventilation
rate at the time of use, as well as other factors such as age, weight,
and the physical condition of the firefighter. Test results indicate that
air was flowing to the facepiece in a sufficient quantity to support moderate
ventilation requirements. It is also important to note that the SCBA facepiece
pressure remained positive throughout the NIOSH Rated Service Time Test.
The Personal Alert Safety
System (PASS) device shipped with the SCBA was not evaluated by NIOSH.
The Institute does not have criteria for testing these units. During the
inspection, the PASS unit was manually activated and appeared to operate
properly.
It is strongly recommended
that this SCBA be inspected and serviced by an authorized MSA service technician,
and all necessary overhaul and repair work be completed before placing
the unit back into service. It is also recommended that all SCBA inspection,
handling, use, and maintenance procedures be reviewed with regard to activities
and practices that could impact the safe use of all SCBA.
It is important to note that
this SCBA is reported to have been left in standing water at the fire scene
for several days following the fire incident. Paper fibers were found adhered
to almost every component of the SCBA. Water was found in the pneumatic
assemblies and inside the SCBA cylinder. It is believed that this contamination
occurred after the victim was removed from the incident scene. It is probable
that the paper fibers and water had an effect on the SCBA’s performance
during the testing sessions at NIOSH and compromised the value of this
physical evidence.
Therefore, the Institute
recommends that the Fire Department review its policies and procedures
to ensure the use of proper methods for maintaining the integrity of physical
evidence collected during fire investigations. Care should be taken to
protect the value of physical evidence from the time of its initial discovery
and collection to its subsequent examination and testing. Guidelines for
the proper handling of physical evidence can be found in NFPA 921, Guide
for Fire and Explosion Investigations, 1998 Edition, Chapter 9 - Physical
Evidence.
No further action will be
taken by NIOSH and the investigation of Task Number TN-11336 will be considered
closed. The SCBA will be stored under lock in room 178A of the NIOSH Appalachian
Laboratory for Occupational Safety and Health (ALOSH) pending return to
the Fire Department.
I trust this information
is satisfactory to meet your needs. If you require further assistance,
please contact me at (304) 285-6337.
Sincerely yours,
Thomas W. McDowell,
Physical Scientist
Quality Assurance Team
Respirator Branch
Division of Respiratory
Disease Studies
ATTACHMENT 2
(This attachment was originally
sent as an official letter summarizing the results of a NIOSH evaluation
of the fire department's SCBA maintenance program.)
DEPARTMENT OF HEALTH &
HUMAN SERVICES
Public Health Service
Centers for Disease Control
aand Prevention (CDC)
National Institute for
Occupational Safety and Health - ALOSH
1095 Willowdale Road
Morgantown, WV 26505-2888
NIOSH Reference: TN-11336
Phone: (304) 285-5907
Fax: (304) 285-6030
February 1, 2000
Dear Chief :
During our visit to the Fire
Department on January 19, 2000, Tim Merinar and I had the opportunity to
evaluate your fire department’s self-contained breathing apparatus (SCBA)
maintenance program. The objectives of our visit were to evaluate your
SCBA maintenance program and to make recommendations for improvement. This
evaluation consisted of visiting the SCBA maintenance area, interviewing
fire department personnel associated with the maintenance of SCBA, reviewing
SCBA maintenance records and procedures, evaluating the compressed-air
cylinder refilling station located at your training facility, examining
Air Truck 1, and evaluating the compressed-air and oxygen cylinder refilling
stations located at Stations 4, 10, and 18. Our evaluation process benefitted
substantially from the cooperation of your staff. Their cooperation was
instrumental in providing us with information necessary for the evaluation
of your SCBA maintenance program.
Your current SCBA maintenance
program was evaluated and compared to the respirator and SCBA maintenance
requirements listed in the following recognized national standards:
Title 29, Code of Federal
Regulations (CFR) Part 1910.134 known as The OSHA Respirator Standard.
National Fire Protection
Association (NFPA) 1404, Standard for a Fire Department Self-Contained
Breathing Apparatus Program, 1996 Edition.
National Fire Protection
Association (NFPA) 1500, Fire Department Occupational Safety and Health
Program,1997 Edition
American National Standards
Institute, Inc. (ANSI), American National Standard for Respiratory Protection,
ANSI Z88.2-1992.
These standards specify the
minimum benchmark requirements that all fire department respirator programs
should strive to meet or exceed. Compliance with these standards is considered
to be essential to maintain SCBA in a condition meeting the certification
requirements of the National Institute for Occupational Safety and Health
(NIOSH) found in Title 42, Code of Regulation, Part 84, Subpart H, as well
as the National Fire Protection NFPA 1981 Standard on Open-Circuit Self-Contained
Breathing Apparatus for the Fire Service, 1997 Edition. Failure to maintain
your SCBA in an approved condition voids the NIOSH approval until such
time as each affected SCBA can be inspected, serviced, and returned to
an approved condition.
The following areas were
identified within the Fire Department SCBA maintenance program as areas
where improvement is needed in order to comply with the referenced national
standards:
1) The SCBA maintenance program
should be under the direct control of one designated individual who is
a Fire Department employee and who has no other fire fighting or administrative
responsibility. In general, this individual’s area of responsibility could
be tailored to meet the department’s needs, but should include supervision
and control of all aspects of the program including the SCBA preventive
maintenance program, repair, testing, record keeping, and auditing. Our
evaluation revealed that personnel currently responsible for the SCBA maintenance
program have responsibilities in other areas.
Title 29, Code of Federal
Regulations (CFR), Part 1910.134 (the OSHA Respirator Standard) at 1910.134(c)
requires each respirator program to be administered by a suitably trained
program administrator.
It was also noted that several
persons had access to the SCBA repair and spare parts storage areas. This
situation could lead to untrained and unauthorized individuals performing
SCBA repair, as well as producing problems with maintaining an accurate
inventory of replacement parts.
2) A preventive maintenance
program should be established to ensure regularly scheduled preventative
maintenance is conducted on each SCBA at least annually. It is noted that
the Fire Department does not operate a preventive maintenance program but
rather attempts to repair defective SCBA on an as-needed basis.
The OSHA Respirator Standard
29 CFR 1910.134(c)(1)(v); 1910.134(c)(1)(vi); and 1910.134(h) require the
employer to develop and implement a written respiratory protection program
that includes specific procedures and schedules for cleaning and disinfecting,
storage, inspection, maintenance, and repair of respirators used by employees.
NFPA 1404, Chapter 6-1.2
and 6-1.3 require annual inspection and servicing of SCBA by qualified
personnel. Chapter 6-1.3 requires annual servicing to be conducted following
the manufacturer’s recommendations and should include :
a) Disassembly of the SCBA
into major components
b) Flow testing of the regulator
c) Disassembly and cleaning
of the regulator
d) Replacement of worn parts,
or those recommended by the manufacturer in the regulator assembly.
e) Disassembly of the low-air
alarm and cleaning and replacement of component parts as necessary.
f) Cleaning and replacement
of components of the facepiece and harness assembly, and replacement of
component parts as necessary.
g) Reassembly of the entire
SCBA and testing for proper operation of all components.
h) Proper recording of all
performed maintenance on record keeping forms.
NFPA 1404, Chapter 6-2.1
specifies that a preventative maintenance program shall be established
by the authority having jurisdiction for all SCBA used in the organization.
NFPA 1404, Chapter 6-2.2
specifies that the SCBA preventative maintenance program shall be conducted
in order to prevent SCBA malfunction and failures of equipment during use.
NFPA 1500, Chapter 5-3.1
specifies the fire department shall adopt and maintain a respiratory protection
program that addresses the selection, inspection, safe use, and maintenance
of respiratory protection equipment, training in its use, and the assurance
of air quality testing.
NFPA 1404, Appendix A, A-6.2
states that an SCBA should be rebuilt by its manufacturer or by a person
trained and certified by the manufacturer at intervals as recommended by
the manufacturer.
Specific guidelines for determining
and scheduling preventive maintenance actions can best be compiled with
assistance from your SCBA manufacturer. Frequency of complete SCBA overhaul
should be based on the manufacturer’s recommendation. If no manufacturer’s
recommendation is provided, NIOSH recommends that rebuilding of SCBA assemblies
be performed every 3 years.
It is apparent that in order
for the Fire Department to establish a comprehensive preventive maintenance
program, the department will need to acquire additional resources. It would
be impossible for your current SCBA maintenance staff to continue to complete
repairs as well as perform all tasks necessary for comprehensive preventive
maintenance for nearly 300 SCBA.
3) Records should be maintained
for each SCBA, facepiece, and cylinder at the department. During our visit,
we were shown a card filing system where repair and testing information
was maintained for each SCBA and filed according to company assignment.
An electronic file had also been developed to help track cylinder hydrostatic
test schedules and service life dates. NIOSH recommends that the computerized
records system be expanded to address the following standard excerpts:
NFPA 1404, Chapter 2-2.3
specifies that an individual record of each SCBA regulator and harness
assembly shall be maintained. This record shall include the inventory or
serial number, date of purchase, date of manufacture, date placed into
service, location, maintenance and repairs, replacement parts used, upgrading,
and test performance.
NFPA 1404, Chapter 2-2.4
specifies that an individual record of each SCBA cylinder shall be maintained.
This record shall include the inventory or serial number date of purchase,
date of manufacture, date placed into service, location, hydrostatic test
pressure and dates, and any inspection and repairs. The hydrostatic test
dates shall appear on each cylinder according to the manufacturer’s instructions
and applicable government agencies.
NFPA 1404, Chapter 2-2.5
specifies that an individual record of each SCBA facepiece shall be maintained.
This record shall include the inventory or serial number, date of purchase,
location, maintenance and repairs, replacement parts, upgrading, and test
performance.
NFPA 1500, Chapter 2-7.5
specifies that each fire department shall assure that inspection, maintenance,
repair, and service records are maintained for all vehicles and equipment
used for emergency operations and training.
The American National Standard
for Respiratory Protection, ANSI Z88.2-1992, Chapter 10.2 specifies that
inspection records be maintained for each respirator.
The OSHA Respirator Standard
29 CFR 1910.134(c); 1910.134(h)(3)(iv)(A and B); and 1910.134(m) specify
general requirements for record keeping within a respirator program.
4) A program should be developed
to ensure that all SCBA cylinders meet the US Department of Transportation
(DOT) standards for periodic requalification and service life limitations.
These standards are listed in Title 49, Code of Federal Regulations (CFR),
Part 173.34(e). During our visit to Station 18, we observed several SCBA
cylinders in service with expired hydrostatic test dates. A review of the
records kept at the Training Center verified that several in-service cylinders
had past-due hydrostatic test dates. DOT requirements for the composite
aluminum, fiberglass-wrapped cylinders utilized by the Fire Department
require that each cylinder be submitted every three years to a DOT-certified
retester for inspection and hydrostatic testing. The DOT requirements limit
the service life for these cylinders to 15 years from the date of manufacture,
regardless of the last date of requalification.
NFPA 1500, Chapter 5-3.8
specifies that SCBA cylinders shall be hydrostatically tested within the
periods specified by the manufacturers and the applicable governmental
agencies.
NFPA 1404, Appendix A, A-6.2
specifies that breathing gas cylinders be tested as prescribed in Title
49, Code of Federal Regulations (CFR), Part 178, Shipping Container Specification
Regulations.
Title 42, Code of Federal
Regulations (CFR), Part 84.81(a), NIOSH Requirements for Respiratory Protection
Devices requires cylinders used on NIOSH-approved SCBA to meet the minimum
DOT requirements.
5) The Fire Department should
establish a written standard operating procedure for managing SCBA found
to be defective or non-functioning. If a firefighter finds an SCBA in need
of service during use or inspection, the SCBA should be identified with
a tag displaying SCBA identification, information regarding the defect
found or performance problem observed, and appropriate contact information
for the SCBA user. This procedure should also cover the methods to be used
to remove the SCBA from service and to refer the problem to the appropriate
SCBA maintenance personnel. All service performed on the SCBA should then
be documented in the records system.
The OSHA Respirator Standard
29 CFR 1910.134(c)(1)(v) and 1910.134(h)(4) require the employer to develop
schedules and procedures for inspecting respirators and ensuring that respirators
that fail inspection or are otherwise found to be defective are removed
from service.
6) Inspections should be
conducted at least weekly and preferably at the beginning of each work
shift and after each use to ensure that each SCBA is checked for proper
function. During our visit, you indicated that each SCBA is inspected at
the beginning of each work shift but that a written record detailing cylinder
pressure, hardware condition, name, date, and other pertinent information
regarding the inspection of each SCBA is not kept.
The OSHA Respirator Standard
29 CFR 1910.134(h)(3) lists the requirements for respirator inspections.
1910.134(h)(iv)(A and B) list the requirements for documenting each inspection.
NFPA 1404, Chapter 5-1.2
specifies that where fire apparatus is in daily use, an inspection of all
respiratory protection equipment and reserve cylinders on each apparatus
shall be conducted at least daily.
The American National Standard
for Respiratory Protection, ANSI Z88.2-1992, Chapter 10.2 specifies that
the SCBA user shall inspect the respirator, and that a record of inspection
dates shall be kept for each respirator.
7) Annual evaluations of
the SCBA Maintenance Program should be conducted to monitor and evaluate
the effectiveness of the overall SCBA maintenance program.
The OSHA Respirator Standard
29 CFR 1910.134(h)(3)(1)(ix) requires the employer to develop and maintain
as part of the overall written respiratory protection program, procedures
for regularly evaluating the effectiveness of the program.
NFPA 1404, Chapter 8-1.1
specifies that the authority having jurisdiction shall review the organization’s
respiratory protection program annually for the purposes of determining
the need to upgrade or change various aspects of the program.
These recommendations are
based upon the premise that all SCBA are life-saving devices which will
only perform as well as they are maintained. Since they are expected to
function and perform properly each time they are used, it is important
that SCBA maintenance and inspection be given the utmost priority at the
department level.
During our visit, we provided
your SCBA maintenance personnel with a copy of the peer-reviewed document
Respirator Maintenance Program Recommendations for the Fire Service developed
by NIOSH and published in the Journal of the International Society for
Respiratory Protection. We also provided draft copies of generic standard
operating procedures and record keeping forms that may assist you in developing
improvements to your overall SCBA maintenance program.
During our visit, we also
inspected and evaluated three oxygen cylinder refilling stations located
at Stations 4, 10, and 18. Oxygen cylinders are typically refilled for
use in oxygen resuscitators and other emergency medical equipment used
to administer oxygen therapy. The OSHA Respirator Standard 29 CFR 1910.134
as well as the NFPA 1404 Standard for a Fire Department Self-Contained
Breathing Apparatus Program, do not specifically address these types of
medical devices. However, safe handling practices dictate that oxygen refilling
systems as well as oxygen equipment be stored in a clean, dry, air-conditioned
location that is locked to limit access only to those individuals who have
been properly trained and qualified to work with oxygen equipment. All
cleaning, repair, and refilling operations should be conducted using the
appropriate special tools which are cleaned, maintained, and dedicated
only for use on oxygen equipment. The oxygen cylinder refilling stations
that we examined failed to meet the above requirements.
The NIOSH Fire Fighter Injury
Investigation Report 98F-23, Oxygen Regulator Flash Severely Burns One
Fire Fighter - Florida, and the joint FDA and NIOSH Public Health Advisory:
Explosions and Fires in Aluminum Oxygen Regulators both contain a number
of recommendations on safe handling procedures for handling and filling
portable oxygen cylinders. Both documents address special precautions which
should be taken for oxygen cylinder filling stations. A copy of each document
is enclosed.
The Compressed Gas Association
pamphlet CGA G-4 (1996 revision) Oxygen (especially chapter 4) and the
NFPA 53 Guide on Fire Hazards in Oxygen-Enriched Atmospheres, 1994 Edition
are also excellent sources of information on oxygen cylinder storage and
safe handling procedures.
I trust this information
is beneficial to your needs. If you have any questions or require additional
information, please contact me at (304) 285-6337.
Sincerely yours,
Thomas W. McDowell
Physical Scientist
Respirator Branch
Division of Respiratory
Disease Studies